IMMERSION ELECTRIC HEATER
The single-phase immersion electric heater can deliver 1 kW, 2k
W or 3 kW depending on the electrical connections, and must
only be used in immersion, via the water connections provided
on the HWC storage cylinders or the BT, TP and TPS storage
tanks.
The electric heater guarantees Legionella prevention or works
to supplement domestic hot water production at low outside
temperatures.
If used inside the TP storage tanks it can help meet building
heating demand in the event of operation outside of the heat
pump operating limits.
Technical specifications
Power supply 230V/50Hz
Power
1000, 2000, 3000 W (+5%/ -10%); power
in relation to the electrical connection.
Maximum pressure 6 Bar
Max temperature, heating area 300°C
Max temperature, seal area 120°C
Adjustable safety thermostat 9….75°C
Heating element material Incoloy 800
Terminal block protection mate
rial PVC
Threaded attachment 1” ½ M GAS
Gasket ASBERIT 60*48*3
Index of protection IP 44
Indicator light Green; on when heater operating
U
PE
N
"1"
"2"
FU1
FU2
KM1
L1 L2 L3
T1 T2 T3
112
158
181,5
72
118
141
Dimensions - Electrical panel
310
140
M 1” 1/2 GAS
105 x 85
85
16 16
330
GREEN LIGHT
Dimensions - Immersion electric heater
Immersion electric heater
The diagram shown is purely indicative.
AWR MTD2 XE
15