DeLonghi AWR-MTD2-XE Service Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
The diagram illustrates the use of the BT/TP storage tank as a
storage tank on the heat pump return pipe so as to increase the
volume of water available in the system, avoiding excessive
starts and stops.
In this case, make sure the available pressure head of the
pump on the unit is sufficient to guarantee correct system oper-
ation.
Technical specifications
The storage tanks are made from carbon steel plate welded
using the best technology and undergo strict water pressure
tests (9 bars, allowing an operating pressure of 6 bars).
Being a container of water for heating and cooling, this product
does not require internal treatment, while the outside is coated
with rustproof paint.
The tanks are protected on the outside with a closed cell elas-
tomeric foam lining, 50 mm thick, with soft blue PVC exterior fin-
ish, for models BT 100/200 and TP300; polyethylene foam insu-
lation, 10 mm thick, with metallic exterior finish for models
BT35.
Ø308
520
613
210
360
80 8580
65
300 120
100
80
288
1741527815
66
Ø7x20
1” 1/4
1” 1”
1” 1/4
Wall
fastening
bracket
Air vent
Fill/drain
Dimensions - Model BT35
Di
d
5
1E-1G
2
2
1D
3
socket
3
socket
3
socket
also on
opposite side
TOP VIEW
1B
1A
4
B
D
A
C
E FG
K
H tot.
1C
5
45°
45°
I
1F-1H
also on opposite
side
Dimensions - Model BT100, BT200, TP300
The diagram shown is purely indicative.
Volume
Storage tank dimensions
Di d Htot A B C D E F G K I
litres mm
100 500 400 970 100 130 160 280 250 264 264 868 140
200 550 450 1410 100 130 160 280 430 374 386 1298 170
300 700 600 1235 100 130 160 280 320 321 332 1133 200
Volume
Fittings
1 2 3 4 5
litres inch
100 1"1/4 2" 1/2" 1/2" 3/8"
200 1"1/4 2" 1/2" 1/2" 3/8"
300 1"1/4 2" 1/2" 1/2" 3/8"
Pos. Description
1A Heat pump outlet
1B Heat pump return
1C System outlet
1D System return
1E- G Supplementary source outlet
1F-1H Supplementary source return
2 Electric heater attachment
3 Probe socket
4 Drain/load
5 Vent
AWR MTD2 XE
13
HFC 410AAWR_MTD2_XE_0011_0091_201109_EN
Page view 12