DeLonghi AWR-MTD2-XE Service Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
OUTLET ELECTRIC HEATER
The outlet electric heaters are available with power ratings of 3
kW single-phase and 3, 6 and 9 kW three-phase.
Used on the system outlet, these guarantee the heating
demand of the building at low outside temperatures by supple-
menting the heating capacity of the heat pump.
The electric heaters are deactivated as soon as the heat pump
alone can meet heating demand.
Considering that normally the heat pump operates only a short
time at low outside temperatures, operation of the supplemen-
tary heater is also reduced and consequently power consump-
tion is negligible.
Therefore, the system’s seasonal efficiency ratio remains
unchanged.
Wall-mounted installation using the fastening brackets.
0 3
70
30
70
348
260
30
53
120
1
2
3
4
5
6
7
8
9
11 (G 1 1/4 B )
30
100
23158
60
9,5 9,5
22
8
10 (G 1 1/4 B)
Technical specifications
Power supply 230V/50Hz 400V/50Hz
Power 3000 W
3000-6000-9000
W
Maximum pressure 6 Bar
Min/max operating
temperature
5...90°C
Safety thermostat 90 +/- 5°C
Adjustable thermostat 30...70°C
Heating element material Incoloy 800
Threaded attachment 1" 1/4 M GAS
Index of protection IP 55
Indicator light Red; on when heater operating
Dimensions
1 Terminal block cover
2 Safety thermostat manual reset
3 Control thermostat knob
4 Reference for knob full scale
5 Cable gland for control cable
6 Cable gland for power cable
7 Red light, on when the heater is
operating
8 Wall fastening brackets
9 Heater body
10 Water inlet
11 Water outlet
The diagram shown is purely indicative.
AWR MTD2 XE
HFC 410AAWR_MTD2_XE_0011_0091_201109_EN
14
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 57 58