To re-connect the ends of the connector hose
to the internal unit, repeat steps 1 to 6 in rever-
se order. The following precautions should be
observed:
Before passing the connector hose through
the hole in the wall, the threaded ends of
the rapid couplings should be protected
using insulating tape or similar.
Fit the two upper refrigerant couplings to the
two lower couplings and tighten by hand,
ensuring that they are correctly connected.
Then use the spanner to tighten fully.
After connecting the two refrigerant cou-
plings, fasten the brackets.
Check that the refrigerant couplings are
sealed perfectly by wetting the couplings
with a little soapy water. No soap bubbles
should form.
Attention
Connection and disconnection of the refrige-
rant couplings should be carried out by quali-
fied personnel.
INTERNAL UNIT
The internal unit should be installed in the room
to be conditioned. Generally, the ideal position
for the internal unit is under a window. In any
case, it should be positioned near an external
wall.
The internal unit must be perfectly leveled. If
necessary, use the castor stops supplied with
the machine.
The air intake and outlet grilles should not be
obstructed in any way.
EXTERNAL UNIT
The external unit can be positioned on a terra-
ce or balcony. In this case, it is not necessary
to use the fixing brackets.
The external unit can also be mounted on a wall.
In this case, use the special wall-mount brackets.
Alternatively, for temporary installation, the
external unit can be hung as shown in the figu-
re. In this case, use the special support belts
(supplied with the appliance).
The external unit can be installed above or at
the same level as the internal unit, provided
that the difference in height between the two
units does not exceed 1.5 m.
The intake and outlet vents must not be
obstructed.
Leave a space of at least 6 cm. between the
rear of the unit and the wall.
CONDENSATION DRAINAGE
The condensation which forms when the unit is
used for air-conditioning (i.e. in summer) eva-
porates from the external unit.
If the humidity is particularly high, it may be
necessary to fit the condensation discharge
tube (supplied with the machine). In this case,
fit the hose to the coupling on the bottom sec-
tion of the external unit (remove the rubber cap
from the coupling).
When specific applications require it, the con-
densation drainage can be done directly from
the discharge pipe on the back of the unit.
Should this happen, water will be collected into
a tank and automatically removed through a
pump system. Such a pump has to be installed
separately and is available at any air conditio-
ning contractors in your area.
334 mm
249 mm
Rubber cap
Ring
Coupling